What is the catalog # for a 60A/3P 600VAC contactor with 3 NC contacts and a 120VAC coil?

We don`t have one but you may use (2) LC1D65008G6 and parallel connect their coils. The 4 NO contacts and 1 extra NC contact would not be used.