Is the FA100X Circuit Breaker Enclosure suitable for use in Division 1 and Division 2 Hazardous Locations?

Issue:
Application

Product Line:
Enclosed Molded Case Switch - Hazardous Location

Cause:
Application

Resolution:
Yes, the FA100X is suitable for use in Hazardous Locations defined by the National Electrical Code (NEC) as Class I, Groups C & D, Divisions 1 & 2; Class II, Groups E, F & G, Divisions 1 & 2; or Class III, Divisions 1 & 2. The device will be marked for Class and Group, but is not required to be marked for Division per NEC 2005 Article 500.8(B)(2) FPN (Fine Print Note).
This device is UL Listed and CSA Certified.