On 100Hz systems, what is the magnetic trip threshold multiplier of a C60N?

Apply the following coefficients to increase magnetic threshhold for higher freq:
Hz Coef.
100 1.06
150 1.13
200 1.205
250 1.274
300 1.342
350 1.411
400 1.48