Technical FAQs

Ask a Question

SED361600LSES2D4 - Testing on bench and getting odd primary injection test results.

The SEPITK2 primary injection test kit is required for testing an SED breaker out of the cell. It makes the required secondary connections to make the breaker operate properly. Erratic readings and performance can be expected without it.




CTA-ID : 5410
Was this helpful?
What can we do to improve the information ?