An SE breaker shows CHARGED but when the CLOSE button is pressed the handle drops to the bottom of the pocket with a ``twok`` sound. Breaker does not close and says DISCHARGED. What should I do?

You must complete the last charge stroke all the way to the top of the pocket that the handle sets in. This rare condition occurs only if the last charging stroke is not completed.