Does SquareD/Schneider Electric offer Single Phase Non-Linear Transformers?

Single Phase Special Transformers 

Product Line:
LV Transformers

Applies to Single Phase Transformer products from SquareD/Schneider Electric

Non Linear Transformers are often used in applications with high levels of Harmonic Energy

Technically, there is no such thing as a Single-Phase (1ph) Non-Linear rated Transformer. 1ph Transformers simply need to be rated to carry the maximum current that the load is likely to demand. For example: if you have only one non-linear device, which is the only load (the worst case scenario for a non-linear current draw,) the worst case current peak would be the square root of three times the load's rated current. Thus, if the load were rated for 10 amps at 240 volts, the most you would need is 10*240*1.732=4,157VA or a 5kVA standard 1ph Transformer.

CTA-ID : 980