What type of fuse is to be used in the 9070 Type T with field installed fuse block or Type TF control transformer?<br />control, fuse block, protection, FB-3A, FB-3B, FB-2A, FB-2B

1-1/2`` x 13/32`` fuses
Primary: Class CC time delay (rejection type)
Secondary: may be either rejection or non-rejection type
All fusing must be sized according to NEC Article 450-3


CTA-ID : 1387