Can the ground fault feature be defeated for test purposes on the Masterpact NW circuit breaker?

Issue:  
How do you disable the ground fault on a Masterpact breaker for primary injecting?

Product line:  
Power Circuit Breakers

Environment:  
Masterpact NW/NT circuit breakers

Resolution:  
There are two ways to defeat ground fault on the NW breaker.  The hand held test kit or the full function test kit can both defeat ground fault.  If neither of these devices are available then the ``looping method`` will have to be employed while primary injecting.  See FA265488 for more information on the looping method.  