How is a DRK1020 Class R Fuse Kit installed into the correct General Duty safety switch fuse clips?

Issue:
Product design features

Product Line:
General Duty Safety Switches

Environment
Class R fuse kit installation

Cause:
application

Resolution:

The DRK1020 is a rejection pin inserted into a hole in the LINE SIDE fuse clips of a 100 ampere switch, or in the LOAD SIDE fuse clips of a 200 ampere switch. Pliers may be required to insert the rejection pins into the fuse clips. An insertion tab is included with the kit to aid in positioning the rejection pin. Remove the insertion tab once the rejection pin is inserted into the fuse clips. The rejection pins should not be able to be removed once properly installed. Three rejection pins included with each kit.