Is a time delay available for the Masterpact NW/NT undervoltage trip?

Need a delay on standard undervoltage relay (UVR) in breaker.

Circuit Breakers

Applies to Masterpact NW/NT breakers.

To eliminate circuit breaker nuisance tripping during a temporary voltage dips, operation of the undervoltage trip (MN/UVR) delayed.  This function is achieved by adding a external delay unit (either adjustable or non-adjustable) to the undervoltage trip (MN/UVR) circuit.

Yes. Time delay modules can be used with the NW/NT UVR in the following voltages:

Adjustable (adjustable with dial on the front via pocket screw driver):

Volts                            Cat. #

48-60 ac/dc               S33680
100-130 ac/dc           S33681
200-240 ac/dc           S33682
380-480 ac               S33683


100-130 ac/dc           S33684
200-240 ac/dc           S33685