What is the minimum level of current displayed by the new Micrologic x.0A trip units?

MICROLOGIC A trip units provide continuous current measurement from 0.2 to 20 x In with an accuracy of 1.5% (including sensors). No auxiliary source is needed where I > 0.2 x I n . The optional external power supply (24 Vdc) makes it possible to display currents where I < 0.2 x I n and to store values of the interrupted current.

CTA-ID : 7975