Can the thermal memory or thermal imaging on an NW Micrologic trip unit be defeated for primary injection testing?

The Handheld Test Kit (HHTK) or Full Function Test Kit (FFTK) may be used to reset the thermal memory. The memory will reset in 20 minutes without a test kit.