How do I test the battery on the Micrologic 5.0A trip unit?

Indication lights working on micrologic trip unit? Test Battery?

Product Line:
Circuit Breakers

Applies to breakers with micrologic trip units with trip indication,  3.0A, 5.0A, 5.0P,5.0H,  6.0A, 6.0P, and 6.0H

Trip indication not working

Press the Test/Reset button to the left of the fault indicator lights. If the lights illuminate, then the battery is good.

Test procedure located in instruction manuals for trip unit in technical library:

48049-136-xx      Ammeter Trip Unit
48049-137-xx      Power Trip Unit
48049-138-xx      Harmonic Trip Unit

CTA-ID : 7952