What are the shunt trip characteristics for the Powerpact P-frame, R-frame, and NS630b - NS3200 electronic trip circuit breakers?

Characteristics:
Vac 24-30, 48-60, 100-130, 200-250, 277, 380-480
Vdc 12, 24-30, 48-60, 100-130, 200-250
Operating Threshold 0.7 to 1.1 Vn
Coil Burden (Holding/inrush) 4.5/200 VA
Power Consumption 4.5 VA
Breaker Resp Time at Vn 50 ms ?10