How do you wire 3 wire control on the ATV18?

Issue: How do you wire 3 wire control on the ATV18?
 
Product Line: ATV18
 
Environment: All
 
Cause: N/A
 
Resolution: Must use interposing relay. Wire +24V through relay contact to LI1. Use another contact as a latching contact in a start/Stop circuit.

 