What does the flashing red LED on the Series B Micrologic Long Time Pick-up mean?

Issue:
What does the flashing red LED on the Series B Micrologic Long Time Pick-up mean?

Product Line:
Circuit Breakers

Environment:
Micrologic Series B

Cause:
This LED sometimes is flashes, and sometimes is steadily lit.

Resolution:
This red LED is an indicator that will flash when the current reaches 90% of the Long Time Pick-up setting, and will be lit continuously when the current is above 100% of the pickup setting. Under normal loads the light will not be on.