How do I unpack a Masterpact NW/NT cradle with circuit breaker, and what tools do I need?

Tools: Hex Key, angled socket wrench, straight blade screwdriver (POZIDRIVE/stotted), Torx 20 screwdriver.
Unpack circuit breaker:
1. Rack circuit breaker to disconnected position.
2. Pressing in latching tabs, pull out on extension rail handles until extension rails are fully extended.
3. Remove circuit breaker.
4. Remove four bolts, nuts and washers securing crable to pallet.
5. Remove cradle from pallet.