What is the replacement for KAL362251595?

Issue:
What is the replacement for KAL362251595?

Product Line:
Legacy Molded Case Circuit Breaker KAL series

Environment:
The KAL Series is obsolete. It can be replaced with the PowerPact J frame. Any operating mechanisms would also have to be replaced and if the K frame was in a MCC bucket then the entire bucket will have to be replaced.

Cause:
A replacement is needed for the KAL362251595 since it is obsolete.

Resolution:
1595 is a combination of 2a2b auxiliary switches and 120Vac under voltage trip (UVR).
The replacement for the KAL breaker  would be a JDL36225 or JGL36225 (depending on the AIC rating desired) and (2) S29450 Auxiliary switches or use suffix AB and (1) S29406 120Vac UVR coil or order or use suffix UA ex: JDL/JGL36225ABUA to have the auxiliary switches and UVR factory installed.

The KAL Series is obsolete. It can be replaced with the PowerPact J frame. Any operating mechanisms would also have to be replaced and if the K frame was in a MCC bucket then the entire bucket will have to be replaced.