Testing a GC200E relay. The pick up works properly but the time delay being set at .4 will trip at .1.

Ground fault Memory is the most likely cause of tripping short of the trip curve specified times. Wait at least 1 minute between tests. For more accurate delay results wait 5 minutes between tests.