Is there anyway to get a 120 volt neutral connection on the 240 delta secondary?

There are no provisions for a neutral, or center tapped winding, connection on the delta winding. It must be ordered as a center tapped delta secondary (ex. 75T6HCT where the CT denotes a ``Center Tap``)
Warning: The capacity of the center tap of the secondary is limited to 5% of the nameplate kVA capacity of the transformer (ex. on the 75T6HCT, nameplate is 75kVA, thus 75,000*.05=3,750VA or 3.75kVA at 120volts, or only 31.25 amps)