Technical FAQs

Ask a Question

Can a Buck & Boost Transformer be used to change 240V to 277V?

277V is sometimes necessary from a 240V source

Product Line:
LV Transformers

Applies to Buck and Boost Transformers by SquareD/Schneider Electric

277V is a common voltage for Fluorescent Lighting Ballasts


Yes, Buck & Boost Transformers can be wired for 13.3% change to boost 240V to 272V using wiring diagram #4 in the Buck & Boost Transformer literature, or the Online Buck and Boost Calculator.  See link below.
WARNING: This connection will usually result in both lines being `live`. Some 277V Fluorescent Lighting Ballasts and maintenance personnel who work on them expect one of the lines to be a neutral with insignificant voltage to ground. Load equipment damage or personal injury could result in such applications.

CTA-ID : 239

Was this helpful?
What can we do to improve the information ?