Technical FAQs

Ask a Question

What does the Trip Class 10, Class 20, and Class 30 mean for overload relays?

Product Line:
NEMA style Overload Relays

Resolution:
That at 600% of the maximum thermal unit current rating or 600% of the actual dial setting on adjustable range OLR`s the Class 10 will trip in 10 seconds or less, Class 20 will trip in 20 seconds or less, and Class 30 will trip in 30 seconds or less.

 
Was this helpful?
What can we do to improve the information ?