Are QOU breakers listed for use on a DC voltage system?

Issue:
Do QOU breakers come standard with a DC rating? 

Product Line:
QOU circuit breakers

Environment:
Products sold and supported in the US

Cause: 
Need DC rated QOU breakers

Resolution:
1-pole and 2-pole 10A-70A and 3-pole 10A-60A QOU breakers are rated up to 48V DC. 1-pole 80A-100A, 2-pole 80A-125A, and 3-pole 70A-100A are rated up to 60V DC. They have a 5k rating at their maximum DC voltage.
 