Can a MP Meter-Pak Meter Center be Series Rated with an upstream device(Breaker or Switch)?

Product Design

Product Line:
MP Meter Pak

Short Circuit Current Ratings

Upstream Disconnecting means

No. The MP Meter-Pak Meter Centers are UL Listed as "Suitable ONLY for use Service Equipment" and cannot be used downstream from any type of disconnect(breaker or switch). Each Meter Pak Device has it's own Short Circuit Current Ratings based on the tenant breakers used for the device(See the current digest page or CAD drawing for the tenant breakers and ratings)