How do you reset the ATS48 soft starter back to factory default?

Issue:
How do you reset the ATS48 soft starter back to factory default?

Product Line:
ATS48

Environment:
All 

Cause:
Needs to reset the soft starters parameter back to factory default. 

Resolution:
Programming menu 
RDY arrow down to 
DRC menu
FCS setting set this to Yes  and hold it for 3 seconds. 
Complete now your soft starter is reset back to the factory settings. 