Can AC current be used to test the Powerpact L frame DC breakers?

Product Line:
500 Vdc Powerpact H, J, and L frame breakers

Resolution:
AC current may be used to test these breakers for thermal tripping at 2 In or 1.35 In test per UL-489 SC.
Magnetic trip tests need to be performed using DC current to get accurate results.
 