Technical FAQs

Ask a Question

Video: How to install shunt trip or undervoltage relay on Powerpact P-frame

Issue:
How do you install a shunt trip or an undervoltage relay on a Powerpact P-frame circuit breaker?

Product Line:
Molded Case Circuit Breakers

Environment:
Powerpact P-frame Circuit Breakers

Resolution:

Remove the cover by removing the screws on each side of the breaker. Then, connect the connection piece in the designated area of the breaker by screwing it in. You would then install the shunt or undervoltage in the slot to the right of the handle, labeled "MN UVR MX SHT". You would align it so that the wiring is coming out of the top left of the device and the silver tab is pointing down from the bottom right of the device. You would then plug the connector into the connection piece. For more information, see the attached instruction bulletin or the instructional video below:

[video placeholder]
Was this helpful?
What can we do to improve the information ?