Issue:
How do I install a shunt trip or undervoltage relay on a Powerpact H-frame, J-frame, or L-frame circuit breaker?

Product Line:
Molded Case Circuit Breakers

Environment:
Powerpact H-frame, J-frame, and L-frame Breakers

Resolution:

Make sure the breaker is in the tripped position, remove the accossory cover, and install the shunt or undervoltage in the bottom left slot in the breaker (labeled MN/MX). Push the shunt or undervoltage into the slot until it clicks into place. For more information, see attached instruction bulletin or the instructional video below: