What address can you read on the ATV61 and ATV71 drives to show the current fault using Ethernet TCP IP or Modbus?

Issue:
What address can you read on the ATV61 and ATV71 drives to show the current fault using Ethernet TCP IP or Modbus?

Product Line:
ATV61 and ATV71

Environment:
All 

Cause:
Wants to read current fault of the drive not the fault history.

Resolution:
Address 8606 will show you the current error code of the drive

Parameter conforming to DSP402 profile.
16#0000 : No fault written to memory (nOF)
16#1000 : Capacitor precharge fault (CrF)
or motor overload fault (OLF)
or motor overspeed fault (SOF)
16#2310 : Overcurrent fault (OCF)
16#2320 : Impedant short-circuit fault (SCF)
or power module fault (SCF)
16#2330 : Motor short-circuit fault (to ground) (SCF)
16#2340 : Motor short-circuit fault (phase to phase) (SCF)
16#3110 : Line supply overvoltage fault (OSF)
16#3120 : Line supply undervoltage fault (USF)
16#3130 : Input phase loss fault (PHF)
16#3310 : DC bus overvoltage fault (ObF)
or motor phase loss fault (OPF)
or motor phase loss fault - 3 phases (OPF)
16#4210 : Drive overheat fault (OHF)
16#5520 : EEPROM non-volatile memory fault (EEF)
16#6100 : Internal fault (InF)
16#6300 : Configuration (parameters) incorrect (CFF)
or invalid (CFI)
16#7300 : 4-20 mA fault on AI3 (LFF)
16#7510 : Modbus communication fault (SLF)
16#8100 : CANopen communication fault (COF)
16#9000 : External fault (EPF)
16#FF00 : Auto-tuning fault (tnF)
16#FF01 : Brake control fault (bLF)


 