Technical FAQs

Ask a Question

How to setup an ATV212 drive to start and stop from face display and speed up using an external potentiometer.

Issue:
How to setup an ATV212 drive to start and stop from face display and speed up using an external potentiometer. 

Product Line:
Altivar 212

Environment:
All

Cause:
Wiring and programming

Resolution:
Wiring for potentiometer:
PP for +10VDC
VIB for signal.
CC for common connection

Programming:
Mode and arrow under AUF.
Set CNOD to 1 for main front display start and stop.
Set FNOD to 2 for 0-10VDC from VIB and CC.
Was this helpful?
What can we do to improve the information ?