Technical FAQs

Ask a Question

What are the replacement coil part numbers for NEMA type S contactors and starters?

Issue:
What is the part number for a replacement coil for a Type S device? 

Product Line:
NEMA Type S Starters

Environment:
US Product Lines

Cause:
Product selection / Maintenance

Resolution:
Equipment To Be Serviced Coil prefix. or Class and Type Hz Suffix Number (Complete Coil consists of the Prefix or the Class and Type followed by the suffix) Coil VA
Device Size Type Poles 24V 110-115V 120V 208V 220V 240V 277V 380V 440V 480V 550V 600V Inrush Sealed
8502 8536 8538 8539 8606 8630 8640 8647 8650 8651 8702 8736 8738 8739 8810 8811 8812 8903 00 SA * (series B) ALL 9998SAC 60 23 @ 45 52 @ 54 55 59 @ 62 @ 65 165 33
50 - 45 - - 54 - - - 62 - 65 -
00, 0, 1, 1-P, & 30A SA (series A), SB, SC, & SM ALL 31041400 60 20 @ 42 48 @ 51 52 56 58 60 61 62 245 27
50 22 42 43 - 51 53 - 57 60 @ 62 64 232 26
2 & 60A SD & SP 2 & 3 31063409 60 16 @ 38 44 @ 47 49 53 @ 57 @ 60 311 37
50 17 38 39 - 47 48 - 54 57 - 60 61 296 36
4 & 5 31063400 60 16 @ 38 44 @ 47 49 53 @ 57 @ 60 438 38
50 17 38 39 - 47 48 - 54 57 - 60 61 429 37
3 & 100A SE & SQ 2 & 3 31074400 60 16 @ 38 44 @ 47 49 53 @ 57 @ 60 700 46
50 17 38 39 - 47 48 - 54 57 - 60 61 678 47
4 & 5 31091400 60 - @ 38 44 @ 47 49 23 @ 57 @ 60 1185 85
50 - 38 39 - 47 48 - 54 57 58 60 61 1260 89
4 & 200A SF &SV ALL 31091400 60 - @ 38 44 @ 47 49 53 @ 57 @ 60 1185 85
50 - 38 39 - 47 48 - 54 57 58 60 61 1260 89
5 & 300A SG & SX series A ALL 31096400 60 - @ 09 15 @ 18 19 21 @ 24 @ 29 2970 212
50 - 09 10 - 18 - - 22 24 - 29 30 2970 250
SG & SX series B ALL 31096320 60 - 50 50 51 52 52 53 54 55 55 - - 1300 14
50 - 50 50 - 52 52 - 54 55 55 - - - -
6 & 7  SH & SJ 2-3 Coil part number 3110440050 (All system voltages) 1780 48
400A, 600A, & 800A SY SZ & SJ (Elect. Held) 1960 59
SY SZ & SJ (Mech Held) 2-3 31104418 60 - @ 09 15 @ 18 19 - @ 24 @ 29 1530 -
50 - 09 - - 18 - - - 24 - 29 - 1250


@ - use a 60 Hz coil of the next higher voltage
Was this helpful?
What can we do to improve the information ?