Can you order two keys for a Kirk Key interlock setup with only one lock?

Issue:  
Can I have multiple keys for my Kirk Key interlock system in which there is only one lock on each device?  

Product line:  
Distribution equipment including switchboards, panelboards, and breakers

Environment:  
Square D distribution equipment

Resolution:  
NO.  The concept of a key interlock is to only have one key so only one breaker can be operated at a time.  Providing more than one key defeats the entire purpose and creates safety risks.  Only one key can be provided.  