Technical FAQs

Ask a Question

How to setup a Fault Status on the Altivar Process Drive?

Issue:
How to setup a Fault Relay on the Altivar Process Drive?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:
You can use any of you drive output relays for programming a run status. Normally R1 relay on the drive is an open/close set of internal contacts and is used for a fault status.
However, the drive has 3 relays and each of them are programmable for a fault status assignment.
Just assign the specific relay to the function "No Drive Fault

Procedure
Follow FAQ below on how to program relays:
FA245321:How are the R1 and R2 and other relays programmed on the Altivar Process Drives? 
 
Was this helpful?
What can we do to improve the information ?