How to upgrade ClearSCADA Mobile?

ClearSCADA Mobile needs to be upgraded after an upgrade of ClearSCADA takes place. To upgrade ClearSCADA Mobile, the following steps need to be followed:
  1. Make a backup of your existing Mobile configuration by making a copy of the "MobileConfig.sdf" file located in "C:\ProgramData\Schneider Electric\ClearSCADA Mobile"
    • This file contains the license information and configuration of the systems and devices
    • Keep a copy of this file in a different location in case it is needed
  2. Uninstall the existing version ClearSCADA Mobile from Windows Control Panel -> Programs and Features
    • Please note that your Mobile configuration should stay untouched even after removing ClearSCADA Mobile as long as the MobileConfig.sdf file is present at the original location
  3. Launch Microsoft Internet Information Services Manager and make sure that "ClearScadaMobile" site is not present
    • If the site is still present after uninstalling ClearSCADA Mobile, remove it manually by right clicking on it and selecting "Remove"
    • Please note that if you are upgrading from ClearSCADA 2015 R1, the mobile site is a part of the "ClearSCADA" site
  4. Launch ClearSCADA installer and select "Install ClearSCADA Mobile" to install the new version of the software and follow the installation steps
  5. Once installed, launch ClearSCADA Mobile Configuration to make sure your original configuration is still present