What is the smallest motor you can run on the ATV630 and ATV930 Process drives?

Issue:
What is the smallest motor you can run on the ATV630 and ATV930 Process drives?

Product Line:
ATV630 and ATV930

Environment:
All 

Cause:
Wants to run a smaller motor on the larger drive.

Resolution:
The nominal motor current can be set to 25% of the drives current rating and the motor thermal can be set to 20% of the drives current ratings. 