What is the power consumption of the RES Remote Reset for NT and NW Breakers?

Issue:
In a Masterpact NT and NW circuit breaker, what is the power consumption of the RES Remote Reset?

Product Line:
Circuit Breakers

Environment:
Applies to Masterpact NT and NW circuit breakers

Resolution:

The Remote Reset (RES) is an optional accessory for Masterpact NT and NW breakers.
The following shows the power consumption of the RES.
  • RES power consumption = 250VA
  • RES inrush current = (250VA/voltage)
  • RES duration of impulse to energize the coil = 1.2 sec