What is the replacement for AP406 Busway ?

Issue:
What is the replacement for AP406 Busway ?

Product Line:
Pre I Line 1 Busway

Environment:
Maintenance

Cause:
Replacement 

Resolution:
Replacement is a 100% neutral rated AP50610 Busway . The AP406 Busway was 4 wire , with only a 50% rated neutral. Teh ne AP50610 will match right up to existing with no other mounting adapters, or accessories needed