ATV630: How do you set the Current Limitation in the drive?

Issue:
 ATV630: How do you set the Current Limitation in the drive?

Cause:
 n/a

Resolution:
Go to menu 5.2 ( Motor Parameters)- Select Dual rating- Normal duty- current limit is 1.1 of In, Heavy duty is 1.5 of In.