22 mm selector switch contact blocks

Issue:
What kinds of contact closures are available for a 22mm - ZB4 or ZB5 Selector Switch?

Product Line:
22mm Push Button

Environment:
XB4 XB5 22mm operators 

Cause:
Determine what options are available                         

Resolution:
The ZBE101 and ZBE102 contact blocks can be used on the back of our selector switches, see the tables below to see what configurations can be achieved. 
 
2 position selector switch
Left Side Operation Right Side Operation Contact block guide
O X 1 N.O. (left or right)
X O 1 N.C. (left or right)
 
3 Position Selector Switch
Left Side Operation Center Operation Right Side Operation Contact Block Guide
O O X 1 N.O. (left)
X O X 2 N.O. wire in parallel (side by side)
X O O 1 N.O. (right)
O X X 1 N.C. (right)
X X O 1 N.C. (left)
O X O 2 N.C. wired in series (side by side)





* O indicates a contact being in the open state, X indicates a contact being in the closed state