E-Flex HOA is acting in reverse the Hand is looking at the 4 to 20mA signal and the Auto is looking at the HMI for speed control.

Issue:
E-Flex HOA is acting in reverse the Hand is looking at the 4 to 20mA signal and the Auto is looking at the HMI for speed control.

Product Line:
E-Flex

Environment:
All 

Cause:
Programming is backwards for Ref 1 and Ref 1b.

Resolution:
Set up your Access level to advanced
Menu 1.2 check the status of your logic inputs LI3 your HOA logic input. 
Hand=1
Off=0
Auto=0

Basic programming to match up HOA inputs
REf 1 channel set to AI2
REf 1b channel set to HMI
Profile is SEP
Command switching is channel 1 active