Technical FAQs

Ask a Question

What would cause the A1U1 parameter not to show up in the Fr1 menu on the ATV320 drive?

Issue:
What would cause the A1U1 parameter not to show up in the Fr1 menu on the ATV320 drive?

Product Line:
Altivar ATV320

Environment:
All 

Cause:
Wants to setup the knob as the speed control 

Resolution:
A1U1 will not show up in the Fr1 menu until you assign CHCF to SEP and holding the enter button for 2 seconds. 

 
Was this helpful?
What can we do to improve the information ?