How do I enable the 3rd relay in my Conext Automatic Generator Starter?

Issue:
Having an issue starting a generator without the 3rd relay

Product Line:
Conext Automatic Generator Starter 865-1060

Environment:
Installation process


Resolution:
Setting for 3rd relay needs to be enabled; setting can be found in the unit's Advanced Settings in the Cfg Gen menu

Cause:
Setting is disabled by default