Technical FAQs

Ask a Question

Have the Pedestal and Deadband been reversed on the Process Drives compared to the ATV61/71 drives?

Issue:
Have the Pedestal and Deadband been reversed on the Process Drives compared to the ATV61/71 drives? 
 
Product Line:
ATV630
 
Environment:
Pedestal and deadband
 
Cause:
n/a
 
Resolution:
Response from France: 
We are aware about that and we are waiting for the solution.
Appears to be a problem on the keypad and SoMove. 
Parameter BSP can have a setting of Standard, Pedestal, Deadband or Deadband 0 % : 
When you see the Keypad: BSP can be standard , Deadband, pedestal or pedestal at 0%: 
The term is inverted on keypad : Deadband should be Pedestal and pededstal /pedestal at 0% should Deadband/Deadband at 0%. 
Same problem with SoMove: 
The solution to set Pedestal like on ATV71, is to set Deadband on ATV6XX/ATV9xx. 
We have asked for a solution on future softwares on the Keypad and SoMove.
Was this helpful?
What can we do to improve the information ?