Where can you wire in a shut down circuit on the ATV660 enclosed drives?

Issue:
Where can you wire in a shut down circuit on the ATV660 enclosed drives?

Product Line:
ATV660

Environment:
All 

Cause:
Wants to wire in a Normally closed contact and shut down the drive if the contact opens. 

Resolution:
You can remove the jumper between terminals 1 and 2 now you can wire in your normally closed contact between terminals 1 and 2.
Please note this is not your normal start and stop circuit. The normal start and stop for drive control is terminals 3 and 4.



 