Do QO, HOM, or Powerpact breakers require no-ox grease when used with aluminum wire?

Product Line:
MCB and MCCB

Resolution:
No-ox grease is not required or recommended on any Square D or Schnedier Electric circuit breakers.  The lugs are designed for use without no-ox, and torque specifications for the lugs are based on dry threads.  If no-ox grease is used, less of the torque energy will be applied to overcoming friction and more will be applied to pressure which may result in stripping the threads. 