How do I disable Output Phase Loss on an ATV320 drive?

Issue:
How do I disable Output Phase Loss on an ATV320 drive?

Product Line:
Altivar 320

Environment:
All

Cause:
N/A

Resolution:
From main menu enter and go down to CONF.
Enter and scroll down to FULL.
Enter and scroll down to FLT-
Enter and scroll down to OPL-
Enter and scroll downt to opl.
Enter and adjust to no from yes to disable.
Enter to save setting.