How are the Basic parameters set up in ATV320 Drive?

Issue:
How are the Basic parameters set up  in ATV320 Drive?

Product Line:
ATV320, Altivar 320

Environment:
All

Cause:
NA

Resolution:
CONF>FULL>SIM
ItH= Motor thermal Current is motor FLA
tFr= Max frequency
ACC= ramp up time
dEC= ramp down time
LSP= Low speed
HSP= High speed

CONF>FULL>drC
bFr= Base motor frequency 60hz
ASY (Async. Motor) press ENT
nPr= HP of he motor
UnS= Rated motor voltage
nCr= Rated motor current (Motor FLA)
FrS= Rated motor frequency
nSP= Rated motor speed (RPM)
Please refer to Programming manual part number  NVE41295