What is the difference between 9012GAW1 and 9012GAW2 diaphragm?

Issue:
What is the difference between 9012GAW1 and 9012GAW2 diaphragm?

Product Line:
Machine Tool, Type G Pressure Switches

Environment:
North American Products

Resolution:
9012GAW1 is used for low pressure application and as such uses a thinner diaphragm but a larger space for it to move the contacts. This has a round plate at the bottom.
9012GAW2 pressure is enough to move the contacts that's why it uses a thicker diaphragm in a smaller space. 