ATV61 or ATV71 drive will not recognize the VW3A3320 card or faults when installed.

Issue: ATV61 or ATV71 drive will not recognize the VW3A3320 card or faults when installed.
 
Product Line: ATV61 and ATV71 drives.
 
Environment: All
 
Cause: Outdated firmware
 
Resolution: Most likely an old firmware version in the drive. Per the VW3A3320 manual: 
The EtherNet/IP card (catalog number VW3 A3320) is used to connect an Altivar 61/71 drive to an Ethernet network using the EtherNet/IP
protocol.
This communication option card is fully supported with the version V5.7 and above of the Altivar 61 firmware and with the version V5.8 and
above of Altivar 71 firmware.