Can you convert a PQ4620G horizontal busway plug in unit to a PS4620G vertical busway unit in the field?

Issue:
Can you change a horizontal bus plug to a vertical bus plug in the field?

Product Line:
Busway 

Environment:
I-line busway fusible and circuit breaker plug in units

Cause:
converting from horizontal mounting to vertical mounting

Resolution:
No. you cannot. Also, these plug in units cannot be mounted for both horizontal and vertical mounting. However, there are some smaller bus plugs where you can add an adapter kit for mounting a horizontal plug in unit for a vertical application or, there are times where you can mount a horizontal plug in unit for both horizontal and vertical applications. You will need to consult with the current Digest (usually in the notes) for adapter kits and or additional mounting options.

 